Final | 6/10/2008 | 6/10/2008 | 6/10/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok to final
|
Electrical Rough-In | 5/19/2008 | 5/19/2008 | 5/19/2008 | P | PASS |
Bob Reichert
|
|
|
light capsulation & potential plane inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers equipotential plane and potting only ok
|
Electrical Rough-In | 5/6/2008 | 5/7/2008 | 5/7/2008 | A | PASS |
Bob Reichert
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers u/g only ok to cover, corrections made
|
Final | 5/5/2008 | 5/6/2008 | 5/6/2008 | A | CANC |
Bob Reichert
|
|
|
cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers see ri
|
Electrical Rough-In | 5/5/2008 | 5/6/2008 | 5/6/2008 | A | FAIL |
Bob Reichert
|
|
|
cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers called, left correction notice,NEC 680.10 PVC shall be minimum 18" deep. U/G wiring shall not be within 5' of inside wall of pool wall, 352.26 there shall not be over 4 quarter bends in raceway, 110.26(A)(3) work space shall be clear from grade, 300.5D)(4) raceway subject to damage shall be schedule 80
|
Electrical Rough-In | 4/28/2008 | 4/30/2008 | 4/30/2008 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok pool bonding only
|
Application received | | | 4/28/2008 | | DONE |
|
|
|
This permit was created on the web by Jari Rivers
|