Final | 6/12/2008 | 6/13/2008 | 6/13/2008 | A | PASS |
William E Thomas
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe . .1. final ok. . .
|
Final | 6/6/2008 | 6/9/2008 | 6/9/2008 | A | FAIL |
Mike Kinnear
|
|
|
owner will be home Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called contractor, left correction notice, NEC 225.30 each building shall be supplied by only 1 feeder or branch circuit, 250.32 shall install grounding electrode system for greenhouse, 352.30(A) shall secure rnc within 3' of termination, 250.24(A) grounding electrode conductor shall be connected to grounded service conductor, 310.8(D) cables shall be listed as sunlight resistant
|
Permanent Service | 5/5/2008 | 5/6/2008 | 5/6/2008 | P | NR |
Mike Kinnear
|
|
|
Please contact owner at ###-#### for time. Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/w rowdy he is going to resched. this inspection & call for an appointment
|
Application received | | | 5/5/2008 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|