Third Notice ELE | 6/10/2008 | 6/10/2008 | 6/12/2008 | | DONE |
Patricia Smith
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 5/23/2008 | 5/23/2008 | 6/10/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
First Notice | 5/12/2008 | 5/12/2008 | 5/23/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 5/12/2008 | 5/12/2008 | 5/12/2008 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/12/2008 at 10:10:48 AM. Contact: ###-####. ok to final
|
Permanent Service | 5/12/2008 | 5/12/2008 | 5/12/2008 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/12/2008 at 10:10:48 AM. Contact: ###-####. p/s o/h n ok
|
Final | 5/8/2008 | 5/8/2008 | 5/8/2008 | P | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/8/2008 at 8:03:29 AM. Contact: ###-####.
|
Final | 5/7/2008 | 5/7/2008 | 5/7/2008 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/7/2008 at 6:55:10 AM. Contact: ###-####. called, left correction notice, BCC shall affix job id sticker, NEC 310.8(D) insulated conductors exposed to sunlight shall be listed as being sunlight resistant, 408.8 panel shall be dead-front, 230.66 disconnect shall be marked as suitable for service entrance equipment, NOTE: need to see pump and controller
|
Application received | | | 5/6/2008 | | |
|
|
|
|
Issue permit | | | 5/6/2008 | | DONE |
|
|
|
|