Final | 11/20/2008 | 11/20/2008 | 11/20/2008 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok final correction made note esc permit has been finaled
|
Final | 11/18/2008 | 11/18/2008 | 11/18/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams called left correction notice, NEC 110.22 shall identify and label disconnects (main and heaters), 422(B)(1)(2) disposal cord shall not be over 3' long, 250.104 shall bond water piping systems, 680 and BCC shall see u/g before cover to hot tub, shall provide disconnect and receptacle, shall see listing
|
Electrical Rough-In | 6/20/2008 | 6/20/2008 | 6/20/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams ric ok
|
Final | 6/19/2008 | 6/20/2008 | 6/20/2008 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams Inspection cancelled from web by: Jim Williams
|
Permanent Service | 5/11/2008 | 5/12/2008 | 5/12/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s u/g n ok
|
Permanent Service | 5/6/2008 | 5/7/2008 | 5/7/2008 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams see conference
|
Conference | 5/7/2008 | 5/7/2008 | 5/7/2008 | A | DONE |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams met contractor, talked about sub-panel clearance requirements and piping interferences for basement panel, rest ok, will recall for p/s
|
Application received | | | 5/6/2008 | | DONE |
|
|
|
This permit was created on the web by Jim Williams
|