Telephone call | | | 9/10/2008 | | DONE |
|
|
|
lft vm with DES ###-#### about the final value at 1:55 pm
|
Third Notice ELE | 7/30/2008 | 7/30/2008 | 8/7/2008 | | DONE |
Darla L Downs
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 7/14/2008 | 7/14/2008 | 7/30/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
First Notice | 6/18/2008 | 6/18/2008 | 7/14/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 6/18/2008 | 6/18/2008 | 6/18/2008 | P | PASS |
Bob Reichert
|
|
|
Zach Phone #: ###-#### ok to final, no card to sign, no esc
|
Rough-In Permanent Service | 5/8/2008 | 5/8/2008 | 5/8/2008 | P | PASS |
Bob Reichert
|
|
|
zach Phone #: ###-#### corrections made, ric ok, p/s, o/h, rec, ok
|
Rough-In Permanent Service | 5/7/2008 | 5/8/2008 | 5/8/2008 | A | FAIL |
Bob Reichert
|
|
|
Zack call if not open Phone #: ###-#### called, left message, left correction notice, nec 250.56 shall augment single electrode by one additional electrode, 110.26(A)(3) work space shall be clear from grade-move phone box under panel at service, 334.30(A) shall strap rmc within 3' of panel, 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members
|
Application received | | | 5/7/2008 | | |
|
|
|
|
Issue & PRINT permit | | | 5/7/2008 | | DONE |
|
|
|
|