ELE-Aging Inspection | 1/29/2010 | 1/29/2010 | 1/29/2010 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 1/29/2010 | 1/29/2010 | 1/29/2010 | P | PASS |
Jack Frank
|
|
|
no activity
|
Final | 6/30/2008 | 7/1/2008 | 7/1/2008 | A | FAIL |
Jack Frank
|
|
|
This is a swimming pool. The inspection needed is final. Thx! Internet Inspection Request from: Chris Weimar corr called left message 110.26(F)(1) shall remove gas pipe from below subpanel for required clearence
|
Electrical Rough-In | 5/28/2008 | 5/29/2008 | 5/29/2008 | A | PART |
Jack Frank
|
|
|
this is a swimming pool. the inspection need is for the potting and equipotential grid. Thanks! Phone #: ###-#### Internet Inspection Request from: Chris Weimar ok no e grid required
|
Electrical Rough-In | 5/22/2008 | 5/23/2008 | 5/23/2008 | A | PASS |
Bob Reichert
|
|
|
This is a swimming pool. The inspection needed if for underground. Thanks Phone #: ###-#### Internet Inspection Request from: Chris Weimar u/g ok
|
Electrical Rough-In | 5/15/2008 | 5/16/2008 | 5/16/2008 | A | PART |
Jack Frank
|
|
|
This is a swimming pool. The inspection needed is for bonding. Thanks Phone #: ###-#### Internet Inspection Request from: Chris Weimar pool bond ok
|
Application received | | | 5/15/2008 | | DONE |
|
|
|
This permit was created on the web by Chris Weimar
|