Second Notice ELE | 6/26/2008 | 6/26/2008 | 7/14/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
Second Notice ELE | 6/26/2008 | 6/26/2008 | 7/14/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
First Notice | 6/10/2008 | 6/10/2008 | 6/26/2008 | | DONE |
Bob Reichert
|
|
|
|
First Notice | 6/10/2008 | 6/10/2008 | 6/26/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 6/10/2008 | 6/10/2008 | 6/10/2008 | P | PASS |
Bob Reichert
|
|
|
corrections made, ok to final, signed card
|
Final | 5/29/2008 | 5/30/2008 | 5/30/2008 | A | PART |
Bob Reichert
|
|
|
Donny Phone #: ###-#### main part electrical ok , left correction notice,reviewed with contractor and electrician. BCC no violations shall be retained, NEC 358.30 emt shall be strapped within 3' of termination, 330.30 mc shall be strapped within 12" of box, 408.4 circuit diectory shall be clear, concise, definitive, 110.26 shall provide work space about electrical equipment, 110.12(A) shall install covers on boxes, 725.3(B) abandoned class 2&3 cables shall be removed, 300.11 cable assemblies shall be securely fastened in place- not on grid or tiles, 230.70(B) shall label service disconnect, no esc permit
|
Electrical Rough-In | 5/21/2008 | 5/21/2008 | 5/21/2008 | P | PASS |
Bob Reichert
|
|
|
donny Phone #: ###-#### front area walls only ok to cover
|
Application received | | | 5/21/2008 | | |
|
|
|
|
Override - People Holds | | | 5/21/2008 | | |
|
|
|
|
Issue permit | | | 5/21/2008 | | |
|
|
|
|
Third Notice ELE | 7/14/2008 | 7/14/2008 | | | |
|
|
|
Second Notice has not been responded to.
|
Third Notice ELE | 7/14/2008 | 7/14/2008 | | | |
|
|
|
Second Notice has not been responded to.
|