Temporary Service | 5/27/2008 | 5/28/2008 | 5/28/2008 | A | PASS |
Jack Frank
|
|
|
daniel Phone #: ###-#### ok t/s u/g new ok
|
Temporary Service | 5/22/2008 | 5/23/2008 | 5/23/2008 | A | FAIL |
Bob Reichert
|
|
|
daniel Phone #: ###-#### called contractor, left message, left correction notice, NEC 350.24(A) shall connect grounded service conductor to grounding electrode conductor, 250.53(G) upper end of ground electrode shall be flush with or below ground, BCC shall correct failed esc- sign, etc
|
Application received | | | 5/22/2008 | | |
|
|
|
|
Issue permit | | | 5/22/2008 | | DONE |
|
|
|
|