Second Notice ELE | 6/26/2008 | 6/26/2008 | 6/26/2008 | | DONE |
Patricia Smith
|
|
|
First Notice has not been responded to.
|
First Notice | 6/2/2008 | 6/2/2008 | 6/26/2008 | | DONE |
Jack Frank
|
|
|
|
Final | 5/30/2008 | 6/2/2008 | 6/2/2008 | A | PASS |
Jack Frank
|
|
|
Jack, we made the changes that we talked about. Please call Mike at ###-#### if there are any other problems. Thanks for the help Internet Inspection Request from: Jamie Winters t/s u/g new ok
|
Temporary Service | 5/29/2008 | 5/30/2008 | 5/30/2008 | A | FAIL |
Jack Frank
|
|
|
PLease call the AME office with any questions or problems ask for Mike or Jamie Internet Inspection Request from: Mike TenHulzen corr called explained violations to contr, ID of high and low voltage seperately derived system GEC shall be done without splice disconnects secondary side of xformer shall not exceed tap off of xformer
|
Application received | | | 5/29/2008 | | DONE |
|
|
|
This permit was created on the web by Mike TenHulzen
|