First Notice | 7/21/2008 | 7/21/2008 | 8/1/2008 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Don Lustig
|
Final | 7/20/2008 | 7/21/2008 | 7/21/2008 | A | PASS |
Bob Reichert
|
|
|
Hello i will stop by with the panel scheduals and general says he is finished Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig corrections made, ok to final, no esc this project, signed occupancy card
|
Final | 7/18/2008 | 7/18/2008 | 7/18/2008 | A | PART |
Bob Reichert
|
|
|
Maybe since no PM''s on Fridays at the mall a latter morning inspection if possible. The owner had to get a couple more missing lights over last night that we have to install. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig met electrician, needs panel schedules and can sign-off, too much other work going on to give temporary occupancy, no esc this project
|
Electrical Rough-In | 7/14/2008 | 7/15/2008 | 7/15/2008 | A | PASS |
Bob Reichert
|
|
|
Hello i secured the flex whip on the center fixtures ready for reinspect.Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig corrections made, ok to finish ceiling cover, no esc this project
|
Electrical Rough-In | 7/14/2008 | 7/14/2008 | 7/14/2008 | A | PART |
Bob Reichert
|
|
|
Hello we are ready for a ceiling grid inspection. Call if any problems or questions thanks. Phone #: ###-#### Internet Inspection Request from: Don Lustig called contractor, told builder ok to cover ceiling except 4 rows in main area. Electrical contractor shall strap mc within 12" of fixtures, 2 rows-center and south row, can see with few tiles left out- will call for am re-inspection, no esc this project
|
Electrical Rough-In | 6/30/2008 | 6/30/2008 | 6/30/2008 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/30/2008 at 9:38:23 AM. Contact: ###-####. walls soffits and hard ceilings ok
|
Electrical Rough-In | 6/27/2008 | 6/27/2008 | 6/27/2008 | P | CANC |
Bob Reichert
|
|
|
Hello contact Andy ###-#### on site he will walk through the job. Were looking for wall and soffit cover. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig called contractor, told no mall inspections in pm and that he has to get permits in order and tied to bld.
|
Owner Supplied Equipment | | | 6/4/2008 | | |
|
|
|
|
Application received | | | 6/4/2008 | | DONE |
|
|
|
This permit was created on the web by Don Lustig
|