Final | 9/12/2008 | 9/12/2008 | 9/12/2008 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### corr. made ok
|
Final | 9/8/2008 | 9/8/2008 | 9/8/2008 | P | FAIL |
Jack Frank
|
|
|
hz Phone #: ###-#### corr. called 210.52(B) remove entry recept from SABC feeding din. rm., 110.3(A) no power tor washer recept, 410.8 clearence NW bed rm closet, 314.16 box fill cutin box right of sink island, 334.15 protect romex in island
|
Reinspection Fee (no hold) | 9/8/2008 | 9/8/2008 | 9/8/2008 | P | DONE |
Jack Frank
|
|
|
hz Phone #: ###-#### corr, job not tested before inspection
|
Rough-In Permanent Service | 6/10/2008 | 6/10/2008 | 6/10/2008 | P | PASS |
Jack Frank
|
|
|
p & h Phone #: ###-#### r/i p/s u/g new ok
|
Application received | | | 6/5/2008 | | |
|
|
|
|
Issue permit | | | 6/5/2008 | | DONE |
|
|
|
|