Second Notice ELE | 3/3/2009 | 3/3/2009 | 5/6/2011 | | DONE |
Jim Toombs
|
|
|
This permit finaled on the web by David Oliver
|
First Notice | 1/8/2009 | 1/8/2009 | 3/3/2009 | | DONE |
Jack Frank
|
|
|
|
Final | 1/7/2009 | 1/8/2009 | 1/8/2009 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith ok
|
ELE-Aging Inspection | 1/7/2009 | 1/7/2009 | 1/7/2009 | | CANC |
Jack Frank
|
|
|
|
Final | 1/7/2009 | 1/7/2009 | 1/7/2009 | A | FAIL |
Jack Frank
|
|
|
called needs grd rods and bond steel, also bond bushing on 3/4 sevice raceway, 5 days to correct
|
ELE-Aging Inspection | 10/31/2008 | 10/31/2008 | 11/3/2008 | | PART |
Jack Frank
|
|
|
see added conf
|
Conference | 11/3/2008 | 11/3/2008 | 11/3/2008 | A | DONE |
Jack Frank
|
|
|
called contr will check on job and call for final
|
ELE-Aging Inspection | 8/7/2008 | 8/7/2008 | 8/8/2008 | | PART |
Jack Frank
|
|
|
waiting for call from contr
|
Final | 6/6/2008 | 6/6/2008 | 6/6/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith corr 250.24(C),300.3(B) 250.32(B)(1) grounded conductor shall terminate at out building service as codes noted state called left # message
|
Reinspection Fee (no hold) | 6/6/2008 | 6/6/2008 | 6/6/2008 | P | DONE |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith corrections again
|
Electrical Rough-In | 6/5/2008 | 6/6/2008 | 6/6/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Smith corr called needs service rated disconnect for out building, 225.31,32,36
|
Application received | | | 6/5/2008 | | DONE |
|
|
|
This permit was created on the web by Kathy Smith
|