VOIDED CHANGE STATUS | | | 6/11/2008 | | DONE |
|
|
|
see ele08-01560 and ele08-01561 - the inspector wanted a permit for both suite 103 and 104
|
Electrical Rough-In | 6/9/2008 | 6/10/2008 | 6/10/2008 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/9/2008 at 9:05:38 PM. Contact: ###-####. walls and hard ceilings ok
|
Electrical Rough-In | 6/9/2008 | 6/9/2008 | 6/9/2008 | P | FAIL |
Bob Reichert
|
|
|
Kubik electric Phone #: ###-#### called left correction notice, NEC edge of bored holes and mc cable shall be 1 1/4" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of boxes, BCC plans and layout do not agree, no esc
|
Application received | | | 6/9/2008 | | |
|
|
|
|
Issue permit | | | 6/9/2008 | | DONE |
|
|
|
|