Second Notice ELE | 7/30/2008 | 7/30/2008 | 8/11/2008 | | DONE |
Patricia Smith
|
|
|
This permit finaled on the web by Celinda Winters
|
First Notice | 7/10/2008 | 7/10/2008 | 7/30/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 7/9/2008 | 7/10/2008 | 7/10/2008 | A | PASS |
Bob Reichert
|
|
|
data cabeling removed by owner - owner told us one data cable to remain as temporary tagged as such and will be removed when permanent data cabling is installed Phone #: ###-#### Internet Inspection Request from: Celinda Winters corrections made, ok to final, signed structural card for 210 only, no esc this project
|
Final | 7/7/2008 | 7/8/2008 | 7/8/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, left correction notice, NEC 358.30(A) shall support emt within 3' of box, 330.30(B) mc shall be secured within 12" of box, 300.11 shall not use grid wires for raceway support, 725.3 shall remove abandoned low voltage wiring,BCC no violations shall be retained, no cables or wiring shall be supported by grid or tiles,no tie-wraps shall be used to support flex conduit, no esc this project
|
Electrical Rough-In | 6/16/2008 | 6/16/2008 | 6/16/2008 | P | PASS |
Bob Reichert
|
|
|
wall inspection Phone #: ###-#### Internet Inspection Request from: Celinda Winters walls only ok to cover, no esc
|
Owner Supplied Equipment | | | 6/16/2008 | | |
|
|
|
|
Application received | | | 6/16/2008 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|