Final | 11/23/2009 | 11/24/2009 | 11/24/2009 | A | PASS |
Bob Reichert
|
|
|
Jim Phone #: ###-#### ok to final
|
Electrical Rough-In | 11/12/2009 | 11/13/2009 | 11/13/2009 | A | PASS |
Bob Reichert
|
|
|
jim Phone #: ###-#### ric ok rest of shop, south and west area
|
Electrical Rough-In | 4/2/2009 | 4/3/2009 | 4/3/2009 | A | PASS |
Bob Reichert
|
|
|
Jim Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 3/31/2009 | 3/31/2009 | 3/31/2009 | P | FAIL |
Jack Frank
|
|
|
Jim Phone #: ###-#### met owner corr posted 250.148(D) grd or replace metal mud rings on plastic boxes, 255.119 shall not ID #6 or smaller eguip grd in feeder conduit from house to shop, 410.62 (C) elect discharge fixtures shall be located dirtly below recept, 110.3(A&B) shall use use boxes listed fro ceiling use, and replace all damages 2,3 gang boxes with broken clamps(314.17(A&C),,,,,300.4(G) needs bushinf fo #4 and larger, 250.4(A)(3&4) tighten bond screw at p/s
|
Electrical Rough-In | 3/19/2009 | 3/20/2009 | 3/20/2009 | A | CANC |
Bob Reichert
|
|
|
tim Phone #: ###-#### see conference, wrong type request
|
Conference | 3/20/2009 | 3/20/2009 | 3/20/2009 | A | DONE |
Bob Reichert
|
|
|
tim Phone #: ###-#### met owner, talked about make-up, free length of conductor, 12" and 8" securing of cable out of boxes, extension rings for boxes, box support to be secure, outside lights to be in boxes, horizontal support of mc cable on trusses
|
Rough-In Permanent Service | 12/1/2008 | 12/1/2008 | 12/1/2008 | P | CANC |
Mike Kinnear
|
|
|
Jim Phone #: ###-#### wrong type inspection
|
Conference | 12/1/2008 | 12/1/2008 | 12/1/2008 | P | DONE |
Mike Kinnear
|
|
|
Jim Phone #: ###-#### needs to clean up main service sub connected free air wires. shop sub panel needs to isolate the neut. bond metal building, frame & support service panel properly, use plastic romex connector for ground wire properly mount boxes,& use green screw for metal boxes.
|
Electrical Rough-In | 8/28/2008 | 8/28/2008 | 8/28/2008 | P | PASS |
Mike Kinnear
|
|
|
Jim- early PM- underground Phone #: ###-#### ok cover under ground conduit to out building
|
Application received | | | 6/18/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/18/2008 | | DONE |
|
|
|
|