First Notice | 8/25/2008 | 8/25/2008 | 1/20/2009 | | DONE |
Jack Frank
|
|
|
|
Final | 8/25/2008 | 8/25/2008 | 8/25/2008 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok coorections made no card
|
Final | 8/22/2008 | 8/22/2008 | 8/22/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr. called 210.8(B) all 15&20 amp 125V recepts shall have gfci protection, 110.3(A) some kit recepts show open neutral, 314.3&110.3(B) shall provide bond bushings for all metallic fittings in non-metallic jbox, 314.43 shall not use screws inside of non-metallic jbox
|
Reinspection Fee (no hold) | 8/22/2008 | 8/22/2008 | 8/22/2008 | P | DONE |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr.
|
Electrical Rough-In | 7/8/2008 | 7/9/2008 | 7/9/2008 | A | PART |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters walls and hard ceilings ok
|
Permanent Service | 7/8/2008 | 7/9/2008 | 7/9/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s u/g new ok
|
Permanent Service | 7/7/2008 | 7/7/2008 | 7/7/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr called p/s still needs all grds and water bonds installed
|
Permanent Service | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | FAIL |
Jack Frank
|
|
|
wall rough-in Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr called job not ready needs all grds and bond at service, 300.4 nail plates and 11/4" over 360 degrees of bends in ENT outside boxes not flush 300.15(C) fittings for ENT
|
Reinspection Fee (no hold) | 7/3/2008 | 7/3/2008 | 7/3/2008 | A | DONE |
Jack Frank
|
|
|
wall rough-in Phone #: ###-#### Internet Inspection Request from: Celinda Winters fee due corr.
|
Conference | 7/2/2008 | 7/2/2008 | 7/2/2008 | P | DONE |
Jack Frank
|
|
|
met J Schmer at site talked to contr. about having journeyman at site while work is being done
|
Owner Supplied Equipment | | | 6/25/2008 | | |
|
|
|
|
Application received | | | 6/25/2008 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|