Final | 10/31/2008 | 11/3/2008 | 11/3/2008 | A | PASS |
Jack Frank
|
|
|
Kathy - ###-#### please call 30 min prior to arrange for access ok
|
Final | 10/22/2008 | 10/23/2008 | 10/23/2008 | A | FAIL |
Jack Frank
|
|
|
kathy - please call for access Phone #: ###-#### corr fee due called contr has 4 working days to correct violations, 110.26(F)(2) remove plant, sprinkler equipment, and curb shall provide 36" for clearence in front of p/s, 408.4 label all circuits in panels where is furnace circuit?, 210.52(B&C) needs outlet for countertop space left of kit sink, 210.8 needs gfci for outlet left of range, needs inuse covers all outside recepts, 422.31 needs lockout clip for furnace breaker upstairs unit
|
Reinspection Fee (no hold) | 10/23/2008 | 10/23/2008 | 10/23/2008 | A | DONE |
Jack Frank
|
|
|
kathy - please call for access Phone #: ###-#### corr fee due
|
Electrical Rough-In | 7/22/2008 | 7/23/2008 | 7/23/2008 | A | PASS |
William E Thomas
|
|
|
todd Phone #: ###-#### Note: please call call 1 hr prior to inspection to get in the location . .1. ri ok. . .
|
Electrical Rough-In | 7/18/2008 | 7/21/2008 | 7/21/2008 | A | FAIL |
William E Thomas
|
|
|
todd - call for access Phone #: ###-#### . .1. recep spacing all over, 1 1/4 all over, no prints. . .2. service is ok, but have not turned it loose at this time. . .
|
Electrical Rough-In | 7/17/2008 | 7/18/2008 | 7/18/2008 | A | NH |
William E Thomas
|
|
|
todd Phone #: ###-#### . .1. doors locked, unable to enter first floor, no inspection done. Called and talked to contractor. . .
|
Application received | | | 7/1/2008 | | |
|
|
|
|
Issue permit | | | 7/1/2008 | | DONE |
|
|
|
|