Final | 8/8/2008 | 8/11/2008 | 8/11/2008 | A | PASS |
Jack Frank
|
|
|
Richard Phone #: ###-#### no esc final ok
|
Final | 8/8/2008 | 8/8/2008 | 8/8/2008 | P | FAIL |
Jack Frank
|
|
|
Richard Phone #: ###-#### corr. 410.8 needs enclosed fixture MB closet, no power to J tub, 110.3(B) shall use manufactures breakers only
|
Electrical Rough-In | 7/14/2008 | 7/14/2008 | 7/14/2008 | P | PASS |
Bob Reichert
|
|
|
richard Phone #: ###-#### corrections made, ric ok
|
Electrical Rough-In | 7/10/2008 | 7/11/2008 | 7/11/2008 | P | FAIL |
Jack Frank
|
|
|
Richard Phone #: ###-#### corr called 314.16 box fill island, 300.14 6" free length, 314.43 screws and nails in plastic boxes, 110.3(A&B) needs instructions for circuit size jtub and DW, 334.30 staple and secure cables within 8"
|
Reinspection Fee (no hold) | 7/11/2008 | 7/11/2008 | 7/11/2008 | P | DONE |
Jack Frank
|
|
|
Richard Phone #: ###-#### corr.
|
Application received | | | 7/3/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/3/2008 | | DONE |
|
|
|
|