Third Notice ELE | 3/3/2009 | 3/3/2009 | 6/27/2012 | | DONE |
Alexandra L. DeYoung
|
|
|
This permit finaled on the web by chris green
|
Second Notice ELE | 7/30/2008 | 7/30/2008 | 3/3/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
First Notice has not been responded to.
|
First Notice | 7/8/2008 | 7/8/2008 | 7/30/2008 | | DONE |
Bob Reichert
|
|
|
|
Final | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | PASS |
Bob Reichert
|
|
|
ok to final, no esc this project
|
Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: chris green corrections made, p/s o/h rec ok, no esc this project
|
Final | 7/7/2008 | 7/8/2008 | 7/8/2008 | A | CANC |
Bob Reichert
|
|
|
Heather ( office) Phone #: ###-#### wrong type request, see p/s, no esc this project
|
Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 | A | FAIL |
Bob Reichert
|
|
|
Heather ( office) Phone #: ###-#### called,, left correction notice, NEC 250.26 single electrode shall be augmented by additional electrode if resistance is 25 ohms or less, 312.5 shall provide abrasion protection for all conductors entering enclosure, BCC job id sticker shall be posted, NOTE shall provide access to interior, no esc this project
|
(F) Reprint permit | | | 7/7/2008 | | DONE |
|
|
|
|
Application received | | | 7/7/2008 | | |
|
|
|
|
Issue permit | | | 7/7/2008 | | DONE |
|
|
|
|