Final | 9/17/2008 | 9/18/2008 | 9/18/2008 | A | PASS |
Mike Kinnear
|
|
|
mike Phone #: ###-#### ok final
|
Rough-In Permanent Service | 9/3/2008 | 9/3/2008 | 9/3/2008 | P | PASS |
Mike Kinnear
|
|
|
william Phone #: ###-#### ok cover ri p/s o/h n ok
|
Rough-In Permanent Service | 9/2/2008 | 9/2/2008 | 9/2/2008 | P | NR |
Mike Kinnear
|
|
|
William Phone #: ###-#### conf with home owner he needs proper stapling on one box, plastic romex connector for gec, a switch for gable fan, 2 inch imc or rigid conduit for mast. (not emt)
|
Rough-In Permanent Service | 8/13/2008 | 8/14/2008 | 8/14/2008 | P | NR |
Mike Kinnear
|
|
|
William Phone #: ###-#### conf needs make up done, free length of conductors, supporting cable 8 inches from box, ko seals, metal boxes grounding metal boxes, ground needs to be ufer rebar, plastic connector for ground wire, & 1 1/4inch from stub face both sides
|
Application received | | | 7/9/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/9/2008 | | DONE |
|
|
|
|