Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE08-01901
StatusFinaled
Name CENTERS ELECTRIC
Site Address 2779 S LIBERTY RD
Project NameLIBERTY STREET OFFICE/SHOP
Customer Number 
ePlanReview 
Description
Service lights, peceps, and 2 light poles. Per initial cert of value $48,904 - METER B//Cross Ref: Ele08-02493 - split permit per Bob Reichert - Final value for this permit is $19,562.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice12/10/200812/10/20083/3/2009 DONE
DetailsBob Reichert
Final12/9/200812/10/200812/10/2008APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS met contractor, ok to final, signed occupancy card
Electrical Rough-In10/30/200810/30/200810/30/2008PPART
DetailsJack Frank
Please inspect trench and conduit on north side of building. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC ok
Rough-In Permanent Service10/21/200810/21/200810/21/2008PPASS
DetailsBob Reichert
eric Phone #: ###-#### p/s u/g n ok, one response only to esc
Electrical Rough-In10/10/200810/10/200810/10/2008PPASS
DetailsBob Reichert
Please inspect underground conduit from building to parking lot lights. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to cover u/g across parking lot
Rough-In Permanent Service9/9/20089/10/20089/10/2008APART
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok cover walls & hard lid ceilings service not ready t/w eric regarding grounding electrode
Rough-In Permanent Service9/8/20089/8/20089/8/2008PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called, left correction notice, NEC 250.94 shall provide intersystem bonding termination, 110.12(A) unused openings shall be closed in panel, 348.26 there shall not be over 360 degree bends in fmc, 330.30(B) mc shall be secured within 12" of termination, 300.14 there shall be at least 6" free conductor left in each box (mezzanine), 300.4(D) shall provide 1 1/4" to raceway from edge of framing member, 110.26(F)(1) ducts shall not be in dedicated space above panel, BCC shall have approved set of plans on job, separate permit shall be provided for each meter location, shall post job id sticker, shall post job address
Application received  7/10/2008  
Issue permit  7/10/2008 DONE
DetailsAlexandra L. DeYoung
Second Notice ELE3/3/20093/3/2009   
First Notice has not been responded to.