Final | 9/24/2008 | 9/24/2008 | 9/24/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: steve creswell corrections made, ok to final
|
Final | 9/23/2008 | 9/24/2008 | 9/24/2008 | A | FAIL |
Bob Reichert
|
|
|
the door should be open by 8:30. I will be there by 9:00 Phone #: ###-#### Internet Inspection Request from: steve creswell met contractor, left correction notice, NEC 410.16 edge of fixture shall be 12" from edge of storage space- both units, 406.4 receptacle shall be securely mounted-washer shoshone side, 110.22 shall label all disconnects- furnaces, service, 406.5 receptacle faceplate shall completely cover opening west microwave, 344.30 shall strap rmc at riser-service
|
Permanent Service | 7/28/2008 | 7/28/2008 | 7/28/2008 | P | PASS |
William E Thomas
|
|
|
. .1. p/s o/h n ok. . .
|
Electrical Rough-In | 7/27/2008 | 7/28/2008 | 7/28/2008 | P | PASS |
William E Thomas
|
|
|
if you can make this your last inspection I would appreciate it. I should be done by then . Ineed the walls so he can insulate. Phone #: ###-#### Internet Inspection Request from: steve creswell (Both 1901 Shoshone/3039 W Spaulding) . .1. ri ok. . .
|
Conference | 7/23/2008 | 7/24/2008 | 7/24/2008 | A | DONE |
Bob Reichert
|
|
|
I would like to talk about the ground issue I have and the penetrations in the fire wall Phone #: ###-#### Internet Inspection Request from: steve creswell talked about grounding and sub-panel placement, reviewed new code requirements, need for approved plans on job since this job appears to be changing according to electrical contractor
|
Application received | | | 7/16/2008 | | DONE |
|
|
|
This permit was created on the web by steve creswell
|