Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE08-01976
StatusFinaled
Name ACE ELECTRIC
Site Address 10331 W ASPEN MEADOW ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/14/200810/15/200810/15/2008APASS
DetailsJack Frank
ray Phone #: ###-#### ok
Rough-In Permanent Service7/17/20087/18/20087/18/2008APASS
DetailsWilliam E Thomas
Ray Phone #: ###-####
. .1. p/s u/g n ok. . .
. .2. ri ok. . .
Permanent Service7/17/20087/17/20087/17/2008PFAIL
DetailsBob Reichert
ray Phone #: ###-#### called, left correction notice, NEC 250.24 gec shall not splice thru enclosure, but be connected directly to each service point
Electrical Rough-In7/17/20087/17/20087/17/2008PFAIL
DetailsBob Reichert
ray Phone #: ###-#### called, left correction notice, 110.14(A) terminal connections shall ensure a thoroughly good connection (garage), 334.30 nm cable shall not be stapled on edge, and be secured within 12" of panel, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing member, 210.52 (A)(1) receptacles shall be installed such that no point along floor line is over 6' from a receptacle outlet (upper bedroom, nw )
Application received  7/17/2008  
Issue permit  7/17/2008 DONE