Final | 10/14/2008 | 10/15/2008 | 10/15/2008 | A | PASS |
Jack Frank
|
|
|
ray Phone #: ###-#### ok
|
Rough-In Permanent Service | 7/17/2008 | 7/18/2008 | 7/18/2008 | A | PASS |
William E Thomas
|
|
|
Ray Phone #: ###-#### . .1. p/s u/g n ok. . . . .2. ri ok. . .
|
Permanent Service | 7/17/2008 | 7/17/2008 | 7/17/2008 | P | FAIL |
Bob Reichert
|
|
|
ray Phone #: ###-#### called, left correction notice, NEC 250.24 gec shall not splice thru enclosure, but be connected directly to each service point
|
Electrical Rough-In | 7/17/2008 | 7/17/2008 | 7/17/2008 | P | FAIL |
Bob Reichert
|
|
|
ray Phone #: ###-#### called, left correction notice, 110.14(A) terminal connections shall ensure a thoroughly good connection (garage), 334.30 nm cable shall not be stapled on edge, and be secured within 12" of panel, 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing member, 210.52 (A)(1) receptacles shall be installed such that no point along floor line is over 6' from a receptacle outlet (upper bedroom, nw )
|
Application received | | | 7/17/2008 | | |
|
|
|
|
Issue permit | | | 7/17/2008 | | DONE |
|
|
|
|