Final | 7/22/2008 | 7/22/2008 | 7/22/2008 | P | PASS |
William E Thomas
|
|
|
. .1. final ok. . .
|
Permanent Service | 7/22/2008 | 7/22/2008 | 7/22/2008 | P | PASS |
William E Thomas
|
|
|
daryl Phone #: ###-#### . .1. p/s o/h reconnect ok. . .
|
Permanent Service | 7/21/2008 | 7/21/2008 | 7/21/2008 | P | FAIL |
Bob Reichert
|
|
|
darrell Note: sp 69 Phone #: ###-#### called contractor, left correction notice, NEC 352.30(A) pvc shall be secured within 3' of panel,312.5 conductors entering enclosure shall have abrasion protection, 250.94 shall provide intersystem bonding termination at service and additional building, no esc for this project
|
Application received | | | 7/21/2008 | | |
|
|
|
|
Issue permit | | | 7/21/2008 | | DONE |
|
|
|
|