Final | 6/2/2009 | 6/2/2009 | 6/2/2009 | P | PASS |
Bob Reichert
|
|
|
doug Phone #: ###-#### corrections made, ok to final, no esc this project
|
Final | 6/1/2009 | 6/1/2009 | 6/1/2009 | P | FAIL |
Bob Reichert
|
|
|
doug Phone #: ###-#### met owner, left correction notice, NEC 422.31(B)shall provide locking device for water heater to disconnect from circuit and tighten fitting, 422.16(B) length of disposal shall not exceed 36", 210.52(B)(2) there shall be no other outlets on the 2 or more small appliance branch circuits, 406.8(B) rear outside receptacle shall be listed weather resistant and be provided with weatherproof enclosure (in-use cover), no esc this project
|
Electrical Rough-In | 8/19/2008 | 8/20/2008 | 8/20/2008 | A | PASS |
William E Thomas
|
|
|
doug Phone #: ###-#### . .1. ri ok for cover. . .
|
Electrical Rough-In | 8/4/2008 | 8/5/2008 | 8/5/2008 | A | NR |
Mike Kinnear
|
|
|
Doug Phone #: ###-#### missing outlets 1 1/4inch stapling note no esc permit in project
|
Permanent Service | 8/5/2008 | 8/5/2008 | 8/5/2008 | A | PASS |
Mike Kinnear
|
|
|
Doug Phone #: ###-#### p/s o/h reconnect ok
|
Electrical Rough-In | 7/28/2008 | 7/29/2008 | 7/29/2008 | P | FAIL |
Pat Lass
|
|
|
doug Phone #: ###-#### had conf about circuiting, opening up for inspection, free conductor, protection of conductors, stapling, make up, grounding, mast height ,etc.
|
Application received | | | 7/23/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/23/2008 | | DONE |
|
|
|
|