Temporary Service | 8/8/2008 | 8/11/2008 | 8/11/2008 | A | PASS |
Bob Reichert
|
|
|
Lynn ###-#### corrections made, t/s u/g n ok
|
Temporary Service | 8/4/2008 | 8/5/2008 | 8/5/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lynn Solmon called left correction notice, NEC 312.5 GEC abrasion protection shall use equipment listed for use, 408.4 shall provide circuit directory, 406.8(A) shall provide in-use type cover for receptacle, 406.8(B) receptacles shall be listed weather-resistant, 110.3(B) shall vvinstall listed equipment per instructions, 590.6(B) shall provide gfci protection for personnel, no esc this project
|
Application received | | | 8/4/2008 | | DONE |
|
|
|
This permit was created on the web by Lynn Solmon
|