Permit Information
Permit NumberELE08-02212
StatusFinaled
Name NORTHWEST ELECTRICAL
Site Address 7557 W USTICK RD
Project Name 
Customer Number 
ePlanReview 
Description
Temporary Power Pole: Temp Power
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice8/29/20088/29/20083/3/2009 DONE
DetailsMike Kinnear
Temporary Service8/28/20088/29/20088/29/2008APASS
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: Mark Sessions t/s u/g n ok note no esc permit in project
Temporary Service8/27/20088/27/20088/27/2008AFAIL
DetailsJack Frank
Contact is Andy. Phone #: ###-#### Internet Inspection Request from: David Bonner corr called needs grd rods at trailer p/s 250.32, 110.3(B) & 314.3 bond bushings for metallic fittings at non-metallic box , 314.28 jbox trailer too small for straight through pull with splices, use listed for grding or plastic conn for GEC
Temporary Service8/11/20088/11/20088/11/2008PFAIL
DetailsJack Frank
Temp Service Inspection Phone #: ###-#### Internet Inspection Request from: Mark Sessions called conn for GEC, seal unused openings, and not ready called
Reinspection Fee (no hold)8/11/20088/11/20088/11/2008PDONE
DetailsJack Frank
Temp Service Inspection Phone #: ###-#### Internet Inspection Request from: Mark Sessions corr. and not ready
Temporary Service8/7/20088/7/20088/7/2008PNR
DetailsWilliam E Thomas
Contact is Perry. Phone #: ###-#### Internet Inspection Request from: David Bonner
. .1. tp is not put together, just a pile of parts. . .
Application received  8/6/2008 DONE
This permit was created on the web by Mark Sessions
Second Notice ELE3/3/20093/3/2009   
First Notice has not been responded to.