Final | 11/27/2009 | 11/27/2009 | 11/27/2009 | P | PASS |
Doug A Poedy
|
|
|
Linda - late afternoon please - also please call 1/2 hr prior Phone #: ###-####. Ok final.
|
DOC - Permit Finaled | 11/27/2009 | 11/27/2009 | 11/27/2009 | P | PASS |
Doug A Poedy
|
|
|
|
Conference | 9/18/2009 | 9/18/2009 | 9/18/2009 | P | DONE |
Jack Frank
|
|
|
ok
|
Electrical Rough-In | 4/10/2009 | 4/13/2009 | 4/13/2009 | A | PART |
Jack Frank
|
|
|
Linda- first thing AM if possible Phone #: ###-#### ok
|
Permanent Service | 4/13/2009 | 4/13/2009 | 4/13/2009 | A | PASS |
Jack Frank
|
|
|
Linda- first thing AM if possible Phone #: ###-#### p/s u/g rec. ok
|
Permanent Service | 2/5/2009 | 2/5/2009 | 2/5/2009 | P | FAIL |
Jack Frank
|
|
|
linda Note: please call 1/2 hr prior to inspection to meet with Phone #: ###-#### corr. net owner300.4 shall provide bushings for #4 or larger where it enters panel, 312.5 needs plastic conn. for GEC that enters back of panel, shall use #1 alum SER , or install 90 amp max breaker for #2 alum SER, 250.94 needs grd for other services, phone & catv
|
Conference | 12/23/2008 | 12/23/2008 | 12/23/2008 | P | PART |
Jack Frank
|
|
|
linda Phone #: ###-#### owner called I answered his ? over the phone
|
Electrical Rough-In | 12/3/2008 | 12/3/2008 | 12/3/2008 | P | PASS |
Bob Reichert
|
|
|
linda - cover of uffer ground Phone #: ###-#### ok to cover concrete encased electrode
|
Electrical Rough-In | 11/26/2008 | 11/26/2008 | 11/26/2008 | P | PASS |
Bob Reichert
|
|
|
Linda late as possible Phone #: ###-#### ric ok for basement and upstairs room, ok to pour concrete encased electrode
|
Electrical Rough-In | 10/15/2008 | 10/16/2008 | 10/16/2008 | A | FAIL |
Jack Frank
|
|
|
bryan Note: if possible first in the morning Phone #: ###-#### corr met owner make-up not done, needs concrete encased electrode, at footing 20ft #4 copper, address both subpanels, T310.15(B)(6) shall install correct size wire for 100 amp ,or use smaller size breaker , 250.148 shall grd metal boxes
|
Conference | 10/13/2008 | 10/16/2008 | 10/16/2008 | A | CANC |
Jack Frank
|
|
|
bryan Phone #: ###-####
|
Conference | 8/15/2008 | 8/15/2008 | 8/15/2008 | P | DONE |
Jack Frank
|
|
|
Linda Phone #: ###-#### ok
|
Conference | 8/11/2008 | 8/12/2008 | 8/12/2008 | A | DONE |
Jack Frank
|
|
|
linda Note: please if possible first thing in morning Phone #: ###-#### talked with owner told her some NEC requirements for job and to get books on home wiring
|
Application received | | | 8/8/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/8/2008 | | DONE |
|
|
|
|