Permit Information
Permit NumberELE08-02345
StatusFinaled
Name BLACKHAM ELECTRIC
Site Address 608 S PHILLIPPI ST
Project Name 
Customer Number 
ePlanReview 
Description
underground
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/21/20095/22/20095/22/2009APASS
DetailsJack Frank
Homeowner fixed the underground to his gate so all should be ready. Phone #: ###-#### Internet Inspection Request from: Brandon ok
Final3/23/20093/24/20093/24/2009AFAIL
DetailsJack Frank
this is for service inspection from the house to the shop Phone #: ###-#### Internet Inspection Request from: Brandon Blackham c alled 1/2" pvc at p/s attached to non electrical pipe going u/g to electric gate installed by fence and gate contr, note no one home, and has job had a p/s inspection?
Electrical Rough-In8/22/20088/22/20088/22/2008PPASS
DetailsBob Reichert
Under Ground. Late afternoon if possible 3:00 or 4:00 Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g house to garage only ok to cover, corrections made, there are 4 90's from each end above ground, will need some type pulling box or fitting
Electrical Rough-In8/21/20088/22/20088/22/2008AFAIL
DetailsBob Reichert
Brandon underground Phone #: ###-#### called contractor, left correction notice, NEC 300.5 minimum burial depth for pvc shall be 18" to top of raceway
Application received  8/21/2008  
Issue & PRINT permit  8/21/2008 DONE