Final | 5/21/2009 | 5/22/2009 | 5/22/2009 | A | PASS |
Jack Frank
|
|
|
Homeowner fixed the underground to his gate so all should be ready. Phone #: ###-#### Internet Inspection Request from: Brandon ok
|
Final | 3/23/2009 | 3/24/2009 | 3/24/2009 | A | FAIL |
Jack Frank
|
|
|
this is for service inspection from the house to the shop Phone #: ###-#### Internet Inspection Request from: Brandon Blackham c alled 1/2" pvc at p/s attached to non electrical pipe going u/g to electric gate installed by fence and gate contr, note no one home, and has job had a p/s inspection?
|
Electrical Rough-In | 8/22/2008 | 8/22/2008 | 8/22/2008 | P | PASS |
Bob Reichert
|
|
|
Under Ground. Late afternoon if possible 3:00 or 4:00 Phone #: ###-#### Internet Inspection Request from: Brandon Blackham u/g house to garage only ok to cover, corrections made, there are 4 90's from each end above ground, will need some type pulling box or fitting
|
Electrical Rough-In | 8/21/2008 | 8/22/2008 | 8/22/2008 | A | FAIL |
Bob Reichert
|
|
|
Brandon underground Phone #: ###-#### called contractor, left correction notice, NEC 300.5 minimum burial depth for pvc shall be 18" to top of raceway
|
Application received | | | 8/21/2008 | | |
|
|
|
|
Issue & PRINT permit | | | 8/21/2008 | | DONE |
|
|
|
|