Second Notice ELE | 3/3/2009 | 3/3/2009 | 9/3/2009 | | DONE |
Jim Toombs
|
|
|
This permit finaled on the web by Kristopher Wilson
|
First Notice | 1/12/2009 | 1/12/2009 | 3/3/2009 | | DONE |
Bob Reichert
|
|
|
|
Final | 1/9/2009 | 1/12/2009 | 1/12/2009 | A | PASS |
Bob Reichert
|
|
|
Final Re-Inspection. Please contact James Kaptianich @ ###-#### prior to inspection. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson corrections made, ok to final, signed structural card, esc finalled
|
Final | 1/8/2009 | 1/9/2009 | 1/9/2009 | A | FAIL |
Pat Lass
|
|
|
Final Inspection. We would like to schedule this as early as possible on Friday morning. Please contact James Kapitanich on the Jobsite @ ###-####. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson no violations to be retained in areas worked. secure and support everything properly remove abanded cables seal unused openings and install all required covers.
|
Final | 12/22/2008 | 12/24/2008 | 12/24/2008 | A | PART |
Bob Reichert
|
|
|
Final Inspection. Please call James @ ###-#### 24hrs prior to inspection to arrange entry. Contractor must be on site during inspection. James @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson met electrician, need to to see ceilings, and compressor room and starbucks, esc finalled
|
Electrical Rough-In | 11/6/2008 | 11/6/2008 | 11/6/2008 | P | PASS |
Bob Reichert
|
|
|
Rough-In inspection for Sushi/Bakery wall. Please contact Kelly Tarter @ ###-####. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to cover wall only between Sushi and bakery
|
Final | 11/4/2008 | 11/6/2008 | 11/6/2008 | P | FAIL |
Bob Reichert
|
|
|
Final inspection for StarBucks Coffee. StarBucks Coffee will be shuting down their operation @ 2:30pm to facilitate this final inspection. Please call Kelly Tarter @ ###-#### to confirm the inspection can take place @ 2:30pm. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson corrections not made, Starbucks - met contractor, left correction notice NEC 330.30(A) mc cable shall be strapped within 12" of termination (top of ceiling), 400.8 shall not use flexible cord as a substitute for fixed wiring (sign above ceiling),250.86 .shall ground metal boxes, 314.16 shall not overfill boxes (cut-in boxes)
|
Electrical Rough-In | 10/30/2008 | 10/31/2008 | 10/31/2008 | A | FAIL |
Jack Frank
|
|
|
Starbucks coffee final inspection. Please call Kelly @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called told contr about violations on listed and labeled starbucks, I have done 2 other units both had same violations free length of conductors, boxes not grded, box fill (cutins), over 360 degree of bends in raceways and strapping within 12" of boxes for flex and MC note no access to inspect too many customers and employees at the starbucks
|
Electrical Rough-In | 10/15/2008 | 10/15/2008 | 10/15/2008 | P | PASS |
Mike Kinnear
|
|
|
Underground inspection in the Meat & Seafood Department in the back of the store. Please call Kelly Tarter @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok cover under slab conduit in seafood area only
|
Application received | | | 9/5/2008 | | DONE |
|
|
|
This permit was created on the web by Kristopher Wilson
|