Final | 10/7/2008 | 10/7/2008 | 10/7/2008 | P | PASS |
Bob Reichert
|
|
|
Ed- after 3 Phone #: ###-#### looked at listed items, ok to final, no esc this project
|
Final | 10/6/2008 | 10/6/2008 | 10/6/2008 | P | NH |
Jack Frank
|
|
|
final eddie ###-#### called owner out of town he will request inspection
|
Permanent Service | 10/1/2008 | 10/1/2008 | 10/1/2008 | P | PASS |
Mike Kinnear
|
|
|
eddie ###-#### p/s o/h reconnect ok note need to check all grounding again, guy kit, & all make up. no esc permit in in project
|
Permanent Service | 10/1/2008 | 10/1/2008 | 10/1/2008 | P | FAIL |
Jack Frank
|
|
|
eddie Phone #: ###-#### corr meet owner see added pm request, owner will be ready at 3:00 pm 300.10&12 needs 4 locknuts for ridig nipple, complete all grds and bond, use #4 copper for grds and bonds, 110.3(B) use GE breakers only, shall complete all and be ready at 3:00 PM
|
Conference | 9/10/2008 | 9/17/2008 | 9/17/2008 | P | DONE |
Bob Reichert
|
|
|
Ed-Please call at least a half hour prior to inspection Phone #: ###-#### talked about service change requirements, grounding, bring up to code, work space, when to call for inspection
|
Application received | | | 9/10/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/10/2008 | | DONE |
|
|
|
|