ELE-Aging Inspection | 3/17/2009 | 3/17/2009 | 3/17/2009 | | DONE |
Bob Reichert
|
|
|
no activity, job done under other permit, see doc expire
|
DOC - Permit Expired | 3/17/2009 | 3/17/2009 | 3/17/2009 | A | PASS |
Bob Reichert
|
|
|
no activity, job done under other permt, ok to doc expire
|
Electrical Rough-In | 9/15/2008 | 9/15/2008 | 9/15/2008 | A | CANC |
Bob Reichert
|
|
|
underground Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no bld, talked to contractor,wrong address see 7126 w victory
|
Temporary Service | 9/15/2008 | 9/15/2008 | 9/15/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left correction notice,NEC 250.53(G) electrode shall be driven at angle not to exceed 45 degrees, 110.26(A) shall provide width and depth work space about equipment, 406.8(B) receptacles shall be listed "WR", BCC shall post job id sticker, NOTE wrong address- should be 7126, fee due, no esc for this listed project
|
Reinspection Fee (no hold) | 9/15/2008 | 9/15/2008 | 9/15/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see t/s corrections
|
Application received | | | 9/15/2008 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|