Second Notice ELE | 3/3/2009 | 3/3/2009 | 9/9/2011 | | DONE |
Jim Toombs
|
|
|
This permit finaled on the web by Joe Thomas
|
First Notice | 10/23/2008 | 10/23/2008 | 3/3/2009 | | DONE |
Jack Frank
|
|
|
|
Permanent Service | 10/22/2008 | 10/23/2008 | 10/23/2008 | A | PASS |
Jack Frank
|
|
|
Disconnect South side pole lights Phone #: ###-#### Internet Inspection Request from: Joe Thomas p/s u/g new ok
|
Final | 10/23/2008 | 10/23/2008 | 10/23/2008 | A | PASS |
Jack Frank
|
|
|
Disconnect South side pole lights Phone #: ###-#### Internet Inspection Request from: Joe Thomas
|
Permanent Service | 10/21/2008 | 10/22/2008 | 10/22/2008 | A | FAIL |
Jack Frank
|
|
|
Disconnect next to transformer to south of main entrance Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr called needs listed or plastic conn for GEC also shall drive grd rods flush with grade
|
Permanent Service | 10/21/2008 | 10/21/2008 | 10/21/2008 | P | CANC |
Jim Schmer
|
|
|
Bob, Id. Power would like each disconnect stickered for permanent service. Ground rods and labels are installed. Phone #: ###-#### Internet Inspection Request from: Joe Thomas need permit for each disc. jms
|
Final | 10/20/2008 | 10/21/2008 | 10/21/2008 | A | PART |
Bob Reichert
|
|
|
4 parking lot pole lights. Phone #: ###-#### Internet Inspection Request from: Joe Thomas light poles ok, service disconnects require 2 ground rods, called contractor, he will call back for p/s if ipco needs sticker for p/s, no esc this project
|
Electrical Rough-In | 9/18/2008 | 9/19/2008 | 9/19/2008 | A | PASS |
Bob Reichert
|
|
|
Inspection for pole light bases and underground conduit. Each pole light will be fused in the handhole. Phone #: ###-#### Internet Inspection Request from: Joe Thomas per 412 and he talked with contractor, no in-line fuses, looked at u/g only for 4 lights, no base inspection except to count 90's, u/g ok to cover only
|
Application received | | | 9/17/2008 | | DONE |
|
|
|
This permit was created on the web by Joe Thomas
|