First Notice | 3/17/2009 | 3/17/2009 | 3/18/2009 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Debby Ellis
|
ELE-Aging Inspection | 3/17/2009 | 3/17/2009 | 3/17/2009 | | DONE |
Bob Reichert
|
|
|
see final, no esc this project
|
Final | 3/17/2009 | 3/17/2009 | 3/17/2009 | A | PASS |
Bob Reichert
|
|
|
ok to final, no esc this project
|
Permanent Service | 9/22/2008 | 9/22/2008 | 9/22/2008 | P | PASS |
Bob Reichert
|
|
|
re-inspection Pat Gill is contact ###-####0 Phone #: ###-#### Internet Inspection Request from: Debby Ellis corrections made, p/s o/h rec ok, no esc this project
|
Final | 9/19/2008 | 9/19/2008 | 9/19/2008 | P | FAIL |
Bob Reichert
|
|
|
Please call Pat Gill, contact ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis called, left correction notice, NEC 250.53(D)(2) shall supplement electrode with one additional electrode, 250.53(G) upper end electrodes shall be flush with or below ground, 110.3(B) shall not use romex connector for abrasion protection unless plastic, 408.4 shall provide circuit directory, BCC shall post job id sticker, shall post address, no esc this project
|
Owner Supplied Equipment | | | 9/19/2008 | | |
|
|
|
|
Application received | | | 9/19/2008 | | DONE |
|
|
|
This permit was created on the web by Debby Ellis
|