Permit Information
Permit NumberELE08-02638
StatusFinaled
Name ALLOWAY ELECTRIC CO INC
Site Address 4037 N LINDA VISTA AVE
Project Name 
Customer Number41132
ePlanReview 
Description
Electrical Permit - Alteration: Add 3 circuits in garage
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/8/20107/8/20107/8/2010PPASS
DetailsJack Frank
ready for inspection Inspection requested from web by: gary batten Phone #: ###-####
ELE-Aging Inspection6/29/20106/29/20106/30/2010 PART
DetailsJack Frank
wsuc
Final4/26/20104/27/20104/27/2010AFAIL
DetailsJack Frank
now ready for inspection Inspection requested from web by: gary batten Phone #: ###-####. Jack please call homeowner when its finalled. Nancy @ ###-#### or Don @ ###-#### thanks. called corr new violation 314.28 address angle pull distance
Reinspection Fee (no hold)4/27/20104/27/20104/27/2010APASS
DetailsJack Frank
now ready for inspection Inspection requested from web by: gary batten Phone #: ###-####. Jack please call homeowner when its finalled. Nancy @ ###-#### or Don @ ###-#### thanks. fee due more violations created
Final4/23/20104/26/20104/26/2010ACANC
DetailsDoug A Poedy
now ready for inspection Inspection requested from web by: gary batten Phone #: ###-####
Final3/15/20103/22/20103/22/2010AFAIL
DetailsJack Frank
Phone #: ###-####
Reinspection Fee (no hold)3/22/20103/22/20103/22/2010PPASS
DetailsJack Frank
Phone #: ###-#### corr posted fee due
Electrical Rough-In3/15/20103/22/20103/22/2010AFAIL
DetailsJack Frank
ready for inspection Inspection requested from web by: gary batten Phone #: ###-####
corr. called 110.14(A) terminals not listed for more than one conductor at p/s, 200.6 shall not reidentify #6 or smaller neutral, 344.46 1/2" rigid nipple requires bushins
ELE-Aging Inspection3/15/20103/15/20103/15/2010 DONE
DetailsDoug A Poedy
Called and scheduled inspection.
Electrical Rough-In9/26/20089/29/20089/29/2008AFAIL
DetailsJack Frank
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten called added 2 subpanels will not work in violation of NEC also where #10 equip grd used ,it shall bee used to grd all boxes and recepts, shall upgrade p/s or use a method that meets 2008 nec requirements
Application received  9/26/2008 DONE