First Notice | 1/7/2009 | 1/7/2009 | 3/3/2009 | | DONE |
Jack Frank
|
|
|
|
Final | 1/7/2009 | 1/7/2009 | 1/7/2009 | P | PASS |
Jack Frank
|
|
|
terry - please call 1/2 hr prior so he can meet you there Phone #: ###-####ok card signed and documentaion of area verified with engineer statement
|
Conference | 12/18/2008 | 12/18/2008 | 12/18/2008 | P | DONE |
Jack Frank
|
|
|
had conference with contractor, adout violations, inspected field evaluated equipment to the UL field valuation sent to Boise City it all checked has not been altered from original evaluation , I accepted it
|
Final | 12/17/2008 | 12/17/2008 | 12/17/2008 | P | FAIL |
Jack Frank
|
|
|
george Phone #: ###-#### need documentation of area 500.4(A) posted, 210.5(C) ID and permanent labels for branch circuits of 480 V, and 120/208 V, 250.32 GEC foe old xformer, B M C 4-05-33 label and listing for field evaluated equipment that was moved from original location called
|
Reinspection Fee (no hold) | 12/17/2008 | 12/17/2008 | 12/17/2008 | P | PASS |
Jack Frank
|
|
|
george Phone #: ###-#### fee due corrections
|
Electrical Rough-In | 12/5/2008 | 12/8/2008 | 12/8/2008 | A | FAIL |
Jack Frank
|
|
|
george Phone #: ###-#### met contr. BCC 4-05-32 (nec 410.62 (C) needs cord cap and recepts for lights, 500.4 needs documentation for hazardous area (wood working), 250.30 grounding for seperately derived systems, 250.32 building suppied by outside feeder, 225.30,31,32 outside feeder (more than one building, 400.10 needs kellum grips for cords at cord caps,250.90 bonding of sevice, 314.3 metallic raceway in non-metallic box, note needs to attach bld to ele, all equip at site for label and listing 7 working days, may need extension
|
Final | 12/5/2008 | 12/8/2008 | 12/8/2008 | A | FAIL |
Jack Frank
|
|
|
george Phone #: ###-#### not ready
|
Final | 12/5/2008 | 12/5/2008 | 12/5/2008 | P | CANC |
Jack Frank
|
|
|
george Phone #: ###-#### talked with contractor he will reschedule a r/i on 12-08-08
|
Application received | | | 9/26/2008 | | |
|
|
|
|
Issue permit | | | 9/26/2008 | | DONE |
|
|
|
|
Second Notice ELE | 3/3/2009 | 3/3/2009 | | | |
|
|
|
First Notice has not been responded to.
|