Final | 11/12/2008 | 11/12/2008 | 11/12/2008 | P | PASS |
Jack Frank
|
|
|
jared Phone #: ###-#### ok
|
Final | 11/6/2008 | 11/7/2008 | 11/7/2008 | A | FAIL |
Jack Frank
|
|
|
JEROD Phone #: ###-#### corr 210.52(C) needs recept right of sink for countertop space 2ft 4ft rule, 410.2&16 clearence MB closet fixture, 250.148 grd box kit. island, 210.11 (C) (2) outside recpt not allowed on laundry circuit this is the second time I've told contr, needs permit for hot tub , and shall wire hot tub to meet art 680
|
Reinspection Fee (no hold) | 11/7/2008 | 11/7/2008 | 11/7/2008 | A | PASS |
Jack Frank
|
|
|
JEROD Phone #: ###-#### corr. and needs permit for spa wiring
|
Permanent Service | 10/15/2008 | 10/15/2008 | 10/15/2008 | P | PASS |
Jack Frank
|
|
|
jared Phone #: ###-#### p/s u/g rec. ok
|
Electrical Rough-In | 10/2/2008 | 10/3/2008 | 10/3/2008 | A | PASS |
Jack Frank
|
|
|
lars Phone #: ###-#### ok
|
Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 | A | FAIL |
Jack Frank
|
|
|
Lars Phone #: ###-#### called job not ready and corrections, 300.4 nail plates, 334.23 protect cables at both attic accesses, 210.11(C)(2) all recepts in laundry rm shall be on laundry circuit, 406.8(C) outlet not allowed over tub enclosure, install and complete makeup for outside boxes, and terminate 14/2 cable into box in closet
|
Reinspection Fee (no hold) | 10/2/2008 | 10/2/2008 | 10/2/2008 | A | DONE |
Jack Frank
|
|
|
Lars Phone #: ###-#### fee due cprrection and job not ready
|
Application received | | | 10/1/2008 | | |
|
|
|
|
Issue permit | | | 10/1/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|