Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE08-02680
StatusFinaled
Name MOUNTAIN VALLEY ELECTRIC
Site Address 3415 W KIPLING RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Remodel
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/12/20091/13/20091/13/2009APASS
DetailsJack Frank
Lock Box Code 7034
Thanks
Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl survey 210.52(C) outlet for countertop right of refer ok
Final10/7/200810/7/200810/7/2008PCANC
DetailsBob Reichert
dan Phone #: ###-#### wrong type request, see ri and p/s, no esc this project
Rough-In Permanent Service10/7/200810/7/200810/7/2008PPASS
DetailsBob Reichert
dan Phone #: ###-#### corrections made, ri ok, p/s o/h rec ok, no esc this project
Rough-In Permanent Service10/2/200810/2/200810/2/2008PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called, left correction notice, NEC 250.52(A)(1) shall use incoming water pipe as a grounding electrode, 230.24(A) service conductors shall be 8' above roof surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 shall secure nm cable within 12" of box (sub-panel), 210.52(A)(1) shall space receptacles such that no point along floor line is more than 6' from a receptacle outlet, BCC shall change room count to 15 on permit, no esc this project
Application received  10/2/2008 DONE
This permit was created on the web by Dan Rohl