First Notice | 3/19/2009 | 3/19/2009 | 2/15/2011 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Spencer Mclean
|
First Notice | 3/19/2009 | 3/19/2009 | 2/15/2011 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Spencer Mclean
|
ELE-Aging Inspection | 3/18/2009 | 3/18/2009 | 3/19/2009 | | DONE |
Bob Reichert
|
|
|
see final, no esc this project
|
Final | 3/19/2009 | 3/19/2009 | 3/19/2009 | P | PASS |
Bob Reichert
|
|
|
ok to final, no esc this project
|
Electrical Rough-In | 10/3/2008 | 10/6/2008 | 10/6/2008 | A | PASS |
Bob Reichert
|
|
|
Re-inspect rough-in. Please call Jeff at ###-####. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, ri ok, no esc this project
|
Permanent Service | 10/6/2008 | 10/6/2008 | 10/6/2008 | A | PASS |
Bob Reichert
|
|
|
Re-inspect rough-in. Please call Jeff at ###-####. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean corrections made, p/s o/h rec ok, no esc this project
|
Rough-In Permanent Service | 10/3/2008 | 10/3/2008 | 10/3/2008 | P | FAIL |
Bob Reichert
|
|
|
Paul Phone #: ###-#### called, left message, left correction notice, NEC 110.12(A) shall close breaker opening, 358.30 shall strap emt within 3' of panel, 312.5 shall provide abrasion protection for all conductors entering enclosure (meter can), 400.8 shall not use so cord for fixed wiring of structure, 250.52(A) shall provide metal water pipe ground, 250.56 shall augmeny ground rod with 1 additional, BCC no violations shall be retained, no esc this project
|
Application received | | | 10/2/2008 | | DONE |
|
|
|
This permit was created on the web by Spencer Mclean
|