Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE08-02740
StatusFinaled
Name ACTIVE WIRING COMPANY
Site Address 6032 N FIVE MILE RD
Project NameJesus Christ of Latter-Day
Customer Number 
ePlanReview 
Description
Electrical Permit - New: complete wiring for new church
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice7/10/20097/10/20099/25/2009 DONE
DetailsBob Reichert
Final7/10/20097/10/20097/10/2009APASS
DetailsBob Reichert
i think we are ready andy is on site this morning if you can go by and check it out thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to final, signed occupancy card, no esc this project
Electrical Rough-In5/8/20095/8/20095/8/2009PPASS
DetailsJack Frank
This for the final ceilings cover two rooms on the east the large ones with can lights and soffits. Also cover on utility shed wiring east parking lot. Andy has the day off so no electricians are on site so call me with any questions or concerns. Thanks Don Phone #: ###-#### Internet Inspection Request from: Don Lustig both east west entrances, both east rms, ceilings and shed ok
Electrical Rough-In4/28/20094/28/20094/28/2009PPART
DetailsMike Kinnear
ceiling cover side classrooms coordinate with andy on site thanks
Phone #: ###-#### Internet Inspection Request from: Don Lustig ok cover hard lid ceilings except for class rms.
Electrical Rough-In4/23/20094/23/20094/23/2009PPASS
DetailsJack Frank
andy - for the rostrom cover Phone #: ###-#### ok
Permanent Service4/16/20094/16/20094/16/2009APASS
DetailsJack Frank
Panel M ready Main on North of church Phone #: ###-#### Internet Inspection Request from: Don Lustig p/s u/g new ok
Permanent Service4/14/20094/14/20094/14/2009AFAIL
DetailsJack Frank
Main Panel on North of building ready for power
Phone #: ###-#### Internet Inspection Request from: Don Lustig
corr. met contr, 200.2(B) & 250.24 shall terminate GEC to grounded bus and install main bonding jumper or screw, 110.3(A) replace damaged wire at p/s (ringed the wire)300.4(G) & 352.46 provide connectors, of bushings where u/g enters bottom of service job not ready also
Reinspection Fee (no hold)4/14/20094/14/20094/14/2009APASS
DetailsJack Frank
Main Panel on North of building ready for power
Phone #: ###-#### Internet Inspection Request from: Don Lustig fee due corr.
Electrical Rough-In3/30/20093/30/20093/30/2009PPASS
DetailsJack Frank
This is for more underground cover any time you get by Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig all parking lot u/g ok
Electrical Rough-In3/27/20093/27/20093/27/2009PPART
DetailsJack Frank
More parking lot underground. Phone #: ###-#### Internet Inspection Request from: Don Lustig all norht and east parking lot lights ok
Electrical Rough-In3/27/20093/27/20093/27/2009APART
DetailsJack Frank
This is for the chapel and cultrual hall wall and ceiling RI, Also for parking lot underground. Phone #: ###-#### Internet Inspection Request from: Don Lustig ok anop
Electrical Rough-In3/9/20093/9/20093/9/2009PCANC
DetailsJack Frank
Andy Phone #: ###-#### see added AM r/i
Electrical Rough-In3/9/20093/9/20093/9/2009APART
DetailsJack Frank
Andy Phone #: ###-#### walls and hard ceilings anop
Electrical Rough-In2/25/20092/25/20092/25/2009ACANC
DetailsJack Frank
This is for part RI on the Shear Walls so the frammer can continue his framing. Andy on site will show what walls. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig anop
Electrical Rough-In2/6/20092/6/20092/6/2009PPART
DetailsJack Frank
this is for the mezzenne ceiling cover call Andy on site at ###-#### for walk thru Phone #: ###-#### Internet Inspection Request from: Don Lustig walls and ceilings ok anop
ELE-Aging Inspection1/20/20091/20/20091/20/2009 PART
DetailsJack Frank
stopped at site no electrical ready at this time wsuc
Electrical Rough-In11/20/200811/20/200811/20/2008PPART
DetailsJack Frank
Pad underground ready for cover stuff under concrete Phone #: ###-#### Internet Inspection Request from: Don Lustig
all u/g inside of church ok
Electrical Rough-In10/28/200810/28/200810/28/2008APART
DetailsJack Frank
If you can swing by and look at the underground we have in this morning sometime that would be great. Thanks Phone #: ###-#### Internet Inspection
Request from: Don Lustig deep u/g inbuilding ok
Rough-In Permanent Service10/8/200810/8/200810/8/2008PCANC
DetailsBob Reichert
ufer ground Phone #: ###-#### Internet Inspection Request from: Don Lustig wrong type request, see ri
Electrical Rough-In10/8/200810/8/200810/8/2008PPASS
DetailsBob Reichert
ufer ground Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to pour concrete encased electrode
Application received  10/8/2008 DONE
This permit was created on the web by Don Lustig