Case Summary (ELE) | | | 3/16/2009 | | DONE |
|
|
|
|
Case Summary (ELE) | | | 3/16/2009 | | DONE |
|
|
|
|
Final | 1/8/2009 | 1/9/2009 | 1/9/2009 | P | PASS |
Pat Lass
|
|
|
Reinspection Electriac Final Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe
|
Final | 1/7/2009 | 1/8/2009 | 1/8/2009 | P | FAIL |
Pat Lass
|
|
|
Electrical Final Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe fix grounds in recepacles in front room and enclose closet light and move or remove 1.
|
Electrical Rough-In | 11/12/2008 | 11/13/2008 | 11/13/2008 | A | PART |
Pat Lass
|
|
|
Rough-in Inspection on the upstairs ONLY. Please call Jake if you have any questions ###-#### Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ok to cover upstairs cut in boxes have had the holding tabs removed and must be replaced.
|
Final | 11/12/2008 | 11/12/2008 | 11/12/2008 | P | CANC |
Jim Schmer
|
|
|
Pleaes call Jake....Rowdy is out of town. Final Inspection request Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe not right insp wanted r/i jms
|
Rough-In Permanent Service | 10/21/2008 | 10/22/2008 | 10/22/2008 | A | PASS |
Jim Schmer
|
|
|
REINSPECTION - corrections have been made - also the main floor bathroom - right behind the panel - Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe r/i (bath & kit) ok) p/s u/g new ok CHECH TO MAKE SURE ALL ACNDUCTORS ARE IN SEOARATE CONNECTORS, NOT ONE NIPPLE JMS
|
Rough-In Permanent Service | 10/20/2008 | 10/21/2008 | 10/21/2008 | A | FAIL |
Pat Lass
|
|
|
Rough-in Service Inspection Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ground to metal water pipe. nipple between meter and panel not bonded, sealed, or installed with proper lock-nuts on each side of entry into enclosures. underground raceways not inspected. panel not permitted over window well. no esc in project
|
Application received | | | 10/13/2008 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|