First Notice | 12/22/2008 | 12/22/2008 | 12/22/2008 | | DONE |
Jack Frank
|
|
|
This permit finaled on the web by Barbara Szurgot
|
Final | 12/19/2008 | 12/22/2008 | 12/22/2008 | A | PASS |
Jack Frank
|
|
|
If not open, code is 1931 Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok no card
|
Final | 12/18/2008 | 12/19/2008 | 12/19/2008 | P | CANC |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot
|
Electrical Rough-In | 11/10/2008 | 11/12/2008 | 11/12/2008 | A | PART |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot walls and ceilings ok called needs required sign circuit 600.5
|
Permanent Service | 11/5/2008 | 11/6/2008 | 11/6/2008 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot p/s o/h reconnect ok survey all grounding shall be in main panel & make sure sub panel has issulated neutal t/w doug.
|
Electrical Rough-In | 10/20/2008 | 10/21/2008 | 10/21/2008 | A | PASS |
Bob Reichert
|
|
|
Not sure what to call this inspection. It is for the trench for light pole in parking lot. Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot u/g for parking lot light only ok to cover
|
Permanent Service | 10/17/2008 | 10/17/2008 | 10/17/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called still needs clearence for service drop over roof
|
Reinspection Fee (no hold) | 10/17/2008 | 10/17/2008 | 10/17/2008 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called all violations not corrected
|
Permanent Service | 10/15/2008 | 10/15/2008 | 10/15/2008 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corr called 230.24(A) 8ft clearence over roof for drop, shall grd or bond water pipi if metallic, 250.64(E) bond both ends of raceway for GEC, 240.24 panel set too high top breaker space over 6ft 7"
|
Application received | | | 10/15/2008 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|