Final | 4/1/2009 | 4/2/2009 | 4/2/2009 | P | PASS |
Pat Lass
|
|
|
Tony Phone #: ###-####
|
Electrical Rough-In | 11/21/2008 | 11/21/2008 | 11/21/2008 | P | PASS |
Jack Frank
|
|
|
tony Phone #: ###-#### ok
|
Rough-In Permanent Service | 11/21/2008 | 11/21/2008 | 11/21/2008 | P | PASS |
Jack Frank
|
|
|
tony Phone #: ###-#### r/i p/s u/g new ok
|
Electrical Rough-In | 11/20/2008 | 11/21/2008 | 11/21/2008 | A | FAIL |
Pat Lass
|
|
|
tony - please call 1/2 hr prior so he can meet you there Phone #: ###-#### still has box fill and free conductor problems also some nail plates no main bonding jumper
|
Reinspection Fee (no hold) | 11/21/2008 | 11/21/2008 | 11/21/2008 | P | FAIL |
Pat Lass
|
|
|
tony - please call 1/2 hr prior so he can meet you there Phone #: ###-#### not all corections made
|
Rough-In Permanent Service | 11/19/2008 | 11/19/2008 | 11/19/2008 | P | FAIL |
Jack Frank
|
|
|
tony Phone #: ###-#### corr 210.70 where is the outside light for aaaaaamb back door, 314.20 all outside boxes shall be flush with siding at time of r/i 250.8&148 shall use grd screw to grd metal boxes, 110.3(A&B) &110.14 (B) shall use approved tool to crimp grd sleves, and shall be tight, 300.14 shall provide free length as code noted states 314.16 shall correct all box fill, 300.4(A)(1) shall provide nail plates where required for holes
|
Reinspection Fee (no hold) | 11/19/2008 | 11/19/2008 | 11/19/2008 | P | PASS |
Jack Frank
|
|
|
tony Phone #: ###-#### corr fee due
|
Electrical Rough-In | 11/19/2008 | 11/19/2008 | 11/19/2008 | P | CANC |
Jack Frank
|
|
|
tony Phone #: ###-####
|
Application received | | | 10/23/2008 | | |
|
|
|
|
Issue permit | | | 10/23/2008 | | DONE |
|
|
|
|