Final | 12/3/2008 | 12/4/2008 | 12/4/2008 | A | PASS |
Jack Frank
|
|
|
please call 1/2 ahead so builder can meet you there Seth ###-#### Thank You Internet Inspection Request from: Todd Holbrook ok
|
Final | 12/3/2008 | 12/4/2008 | 12/3/2008 | A | CANC |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook Inspection cancelled from web by: Todd Holbrook
|
Rough-In Permanent Service | 11/3/2008 | 11/4/2008 | 11/4/2008 | A | PASS |
Bob Reichert
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook corrections made, ric ok p/s u/g rec ok
|
Rough-In Permanent Service | 10/31/2008 | 10/31/2008 | 10/31/2008 | P | FAIL |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook called all violations not corrected and new violations created 250.8 shall use machine type screws for grd and bonds equip grd bus jbox, nail plates and 11/4" for cables parallel, seal all unsed KOs, 334.30 staple cables within 12" of boxes and cabibets
|
Reinspection Fee (no hold) | 10/31/2008 | 10/31/2008 | 10/31/2008 | P | DONE |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook corr. violations not corrected
|
Rough-In Permanent Service | 10/29/2008 | 10/29/2008 | 10/29/2008 | P | FAIL |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook called corr. and do not cover posted 250.148 j box in closet splice equip grds together, 300.4 nail plates and 11/4" grd pancake box M bath 110.12(A) seal KOs back of meterbase and jbox, 250.52(A)(1) or 104 (A)(1) grd or bond water to p/s remove GEC from jbox and shall not splice it, 334.30 staple cables within 12" of metal boxes shall update permit for 6 rms
|
Application received | | | 10/29/2008 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|