Final | 3/3/2009 | 3/4/2009 | 3/4/2009 | A | PASS |
Mike Kinnear
|
|
|
Call Doug if job is not open Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok final note esc permit has been finaled
|
Electrical Rough-In | 11/4/2008 | 11/5/2008 | 11/5/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corrections made, ric ok, no esc this project
|
Electrical Rough-In | 11/3/2008 | 11/4/2008 | 11/4/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called, left correction notice, BCC no violations shall be retained-closet, basement, - shall provide boxes for fixtures porch entry and microwave, NEC 334.30 nm cable shall be secured within 12" of box- stairwell, 334.15(B) nm cable shall be protected from physical damage-stairwell, 210.52(A)(2) shall provide receptacle in 2' wall space kitchen area, no esc this project
|
Electrical Rough-In | 11/3/2008 | 11/3/2008 | 11/3/2008 | P | CANC |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot Inspection cancelled from web by: Barbara Szurgot
|
Electrical Rough-In | 10/31/2008 | 11/3/2008 | 11/3/2008 | A | NR |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot job not ready fee due
|
Reinspection Fee (no hold) | 11/3/2008 | 11/3/2008 | 11/3/2008 | A | NR |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
|
Application received | | | 10/31/2008 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|