Final | 5/11/2009 | 5/12/2009 | 5/12/2009 | A | PASS |
Bob Reichert
|
|
|
Dave Phone #: ###-#### corrections made, ok to final
|
Final | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | FAIL |
Jack Frank
|
|
|
Dave Phone #: ###-#### corr posted called 334.15 protect 10/2 at W.H., 210.8(A)(7) needs gfci all recepts within 6ft od laundry sink, 410.10 needs shower trim , correct open equip grds left and right of disposal switch wet bar area
|
Reinspection Fee (no hold) | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | PASS |
Jack Frank
|
|
|
Dave Phone #: ###-#### fee due corr not made
|
Final | 4/23/2009 | 4/24/2009 | 4/24/2009 | A | FAIL |
Pat Lass
|
|
|
Dave Phone #: ###-#### contractor did not call for this inspection. receps not tamper resistant and gfci protection required within 6 ft of sinks.
|
Electrical Rough-In | 12/11/2008 | 12/11/2008 | 12/11/2008 | P | PASS |
Pat Lass
|
|
|
Call 30 mins prior to going for access Phone #: ###-####
|
Application received | | | 12/11/2008 | | |
|
|
|
|
Issue permit | | | 12/11/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|