Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE09-00080
StatusFinaled
Name RSI INC
Site Address 2301 N 36TH ST Unit: 102
Project NameTERRY REILLY DENTAL CLINIC
Customer Number 
ePlanReview 
Description
Electrical r/i and trim out for new dental clinic - $37,500 initial cert of value
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice3/27/20093/27/20093/31/2009 DONE
DetailsPat Lass
This permit finaled on the web by HARVEY REYNA
Final3/27/20093/27/20093/27/2009PPASS
DetailsPat Lass
Harvey Phone #: ###-####
Final3/26/20093/26/20093/26/2009PFAIL
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
panels require working clearance.
2 screws required in raised covers.
bond hot water.
GFCIs not working in lab.
prewired cabinets shall be field tested or rewired.
Final3/13/20093/16/20093/16/2009ACANC
DetailsJack Frank
final ceiling reinspection Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA see added r/i
Electrical Rough-In3/16/20093/16/20093/16/2009APASS
DetailsJack Frank
final ceiling reinspection Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok
Final3/13/20093/13/20093/13/2009PFAIL
DetailsPat Lass
ceiling final Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
support mc within 12 in of boxes.
Electrical Rough-In2/18/20092/19/20092/19/2009PPART
DetailsJack Frank
rough-in walls & ceiling Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA all walls and high ceilings
Permanent Service1/29/20091/29/20091/29/2009PPASS
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
P/S U/G R Ok install 2 meters for 1 space
Electrical Rough-In1/19/20091/20/20091/20/2009APART
DetailsPat Lass
underground Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
Application received  1/15/2009  
Issue permit  1/15/2009 DONE