Final | 4/27/2009 | 4/27/2009 | 4/27/2009 | A | PASS |
Mike Kinnear
|
|
|
Code to get in through garage 1234. Thanks!! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn ok final corrections made
|
Final | 4/23/2009 | 4/23/2009 | 4/23/2009 | A | FAIL |
Bob Reichert
|
|
|
Code for garage door 1234. Thanks! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn called, left correction notice, NEC 210.8(A)(6) kitchen countertop receptacles shall be gfci protected, 406.4(D) receptacle faces shall be flush with or project from faceplate (under island countertop),406.4 receptacles shall be securely mounted-front hall, upper north bedroom, Note- front lights dont work
|
Rough-In Permanent Service | 2/4/2009 | 2/4/2009 | 2/4/2009 | A | PASS |
Bob Reichert
|
|
|
Thank You! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn called contractor, met electrician, ric ok, p/s u/g n ok
|
Application received | | | 2/4/2009 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|