First Notice | 5/7/2009 | 5/7/2009 | 5/12/2009 | | DONE |
Bob Reichert
|
|
|
This permit finaled on the web by Barbara Szurgot
|
Final | 5/6/2009 | 5/7/2009 | 5/7/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok to final, signed structural card, no esc this project
|
Final | 5/5/2009 | 5/6/2009 | 5/6/2009 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contractor, needs to finish panel schedules, strap conduit to skid, label breaker what it is for, plug holes in pro-pak,add cover to receptacle below panel, add gfci for vending machines and mixer, rest ok, will recall and then can sign occupancy card, no esc this project
|
Permanent Service | 3/30/2009 | 3/31/2009 | 3/31/2009 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contractor, told him he shall add 1 more ground rod, check later, p/s u/g rec ok, no esc this project
|
Conference | 3/12/2009 | 3/13/2009 | 3/13/2009 | P | DONE |
Bob Reichert
|
|
|
Give Steve a call 1/2 hour prior, if possible. Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot talked with contractor about remodel for damaged building and told him that if calculations allow, then ok to downsize service for load would be ok. Mentioned that service needs to be brought up to code and rest of installation. No esc this project.
|
Owner Supplied Equipment | | | 3/12/2009 | | |
|
|
|
|
Application received | | | 3/12/2009 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|