Final | 3/31/2009 | 3/31/2009 | 3/31/2009 | P | PASS |
Bob Reichert
|
|
|
Paul Phone #: ###-#### p/s o/h rec ok, no esc this project
|
Permanent Service | 3/30/2009 | 3/31/2009 | 3/31/2009 | A | NR |
Bob Reichert
|
|
|
paul ###-#### looks like it probably was yesterday, all comments apply, no esc this project
|
Permanent Service | 3/30/2009 | 3/30/2009 | 3/30/2009 | P | NR |
Jack Frank
|
|
|
paul - late this afternoon please Phone #: ###-#### talked to man at house, called paul left message no response back, job not no grd rods installed yet needs to GEC to u/g water pipe within 5ft, looks like the mast needs to be higner for 10ft clearence from grade to drip loop, and wires in mast not terminated at meter yet
|
Conference | 3/26/2009 | 3/27/2009 | 3/27/2009 | P | DONE |
Bob Reichert
|
|
|
Paul talked about homeowner doing service change, when is better time to do, timing for disconnecting power and inspection to re-connect, grounding, clearances, bring up to code
|
Issue PAID IN FULL permit | | | 3/26/2009 | | DONE |
|
|
|
|
(F) Reprint permit | | | 3/26/2009 | | |
|
|
|
|
Application received | | | 3/26/2009 | | |
|
|
|
|